Product Description
- Full four quadrant metering
- 5 main energy registers
- Load survey recording of: 160 days of 1 channel 30 minute data / 80 days of 2 channel 30 minute data / 53 daysof 3 channel 30 minute data / 40 days of 4 channel 30 minute data / 32 days of 5 channel 30 minute data
- N.B Optional 64k memory increases the data storage typically by a factor of three Load survey integration periods of 5, 15, 30 or 60 minutes
- Maximum demand integration periods of 5, 15, 30 or 60 minutes
- Up to 4 user configurable outputs
- Up to 3 user configurable inputs
- 9600 baud PACT communication port
- 9600 baud modem port under the terminal cover
- 1200 baud IEC1107 communication port
- Ofgem approved to IEC1036 and IEC687
- 16 time of use and 8 maximum demand registers, user configurable for seasonal control over all 5 energy types
|
Premier Technical Specification |
|
|
|
ELECTRICAL Build options available for: CT Connected 230V phase to neutral, 3 element 3 phase 4 wire. CT/VT connected 100/110V phase to phase, 2 element 3 phase 3 wire. CT /VT connected 57.7/63.5V phase to neutral, 3 element 3 phase 4 wire, 2 phase 3 phase 4 wire, 1 phase 3 wire, 1 phase 2 wire. Additional configurations available on request. |
ACTIVITY INDICATOR Format High intensity red LED, kWh consumed. Meter Constant 800 flashed per kWh for 230V 3 phase 4 wire CT connected 100A (scaled for other ratios and voltages). |
|
|
EU DIRECTIVES The product complies with 89/336/EEC Electromagnetic Compatibility Directive, amended by 92/31/EEC, by meeting BS EN 61036:1997. |
||
|
ENVIRONMENTAL* Operating Temperature -10°C to +45°C Storage Temperature -25°C to +70°C Operating Humidity Up to 95% non-condensing * requirements for specific countries available on request |
||
|
CURRENT In 5A 1A Imax 6A 1.2A Additional configurations available on request. |
||
|
TERMINALS Two screws per conductor. Suitable for cable sizes from 2.5mm2 to 5.0mm2 PULSED INPUTS AND OUTPUTS Premier can be supplied in various hardware builds witup to 7 input/output channels, for example: 4 outputs, 0 inputs 4 outputs, 3 inputs The CLEM and tariff files determine the exact functionaof inputs and outputs. The hardware-build determines which inputs and outputs are physically provided. h lity |
||
|
BURDEN ALL MODEL TYPES Current circuit <0.5VA Voltage circuit <0.5VA |
||
|
METROLOGICAL IEC 1036/687 Class Class 2.0S, 1.0S, 0.5S, 0.2S |
||
|
MECHANICAL ALL MODEL TYPES Dimensions W.176 X H.250 X D.67 mm Enclosure Material ABS/Polycarbonate Degree of Protection IP51 Flame Retardation UL 94 V0 Weight (approx.) 1 kg |
||
|
PULSED INPUTS Up to two external parameters can be counted, with thcapability to store values as load survey parameters. Up to two external signals can be used to synchronise time-base or switch time-of-use registers. Inputs are rated for 9-40 Vdc operation. e |
||
|
MAINS FREQUENCY 45-65Hz |
||
|
DATA RETENTION 10 years minimum (unpowered) |
||
|
DISPLAY Format LCD Image Area 75 x 17mm |
PULSED OUTPUTS Up to four outputs can be used to indicate energy consumption, active rate, change of rate, end of demaperiod, or to indicate that a particular rate is active. nd |
|
|
CLOCK & CALENDAR Normal Power Source Mains supply RTC Backup Source Lithium battery or super cap. Battery Life (typical) 10 years Min Shelf Life (typical) 3 years |
||
|
COMMUNICATIONS Local Interrogation ports PACT and 1107 ports Remote Interrogation Optically isolated RS232 port port under the terminal cover Protocol PACT at speeds from 1200-9600 baud |